Start/stop using terminals (External
operation)
The motor will not rotate ... Why?
Check that [EXT] is lit.
[EXT] is valid when Pr. 79 = "0" (initial value).
Use
Check that wiring is correct. Check once again.
Change the frequency (0Hz) of the minimum value of potentiometer (at 0V)
Adjust the frequency in calibration parameter C2 Terminal 2 frequency setting bias frequency. (Refer to
Chapter 4 of
When you want to compensate frequency setting, use terminal 1.
For details, refer to Chapter 4 of
4.5.5
Changing the output frequency (60Hz, initial value) at the maximum voltage
input (5V, initial value)
<How to change the maximum frequency>
Changing example
When you use the 0 to 5VDC input to change frequency at 5V from 60Hz (initial value) to
50Hz, set "50Hz" in Pr. 125.
1.
Turn
until
2.
Press
to show the present set value.
"
"(60.00Hz)
3.
Turn
to change the set value
to "
4.
Press
to set.
5.
Mode/monitor check
Press
twice to choose the monitor/frequency monitor.
6.
To check the setting, turn the start switch (STF or STR) ON
and input 5V (turn the potentiometer clockwise slowly to full.)
(Refer to 4.5.4 steps 2 to 5)
The monitor on the operation panel or the frequency meter (indicator) connected across terminals FM and SD does
not indicate exactly 50Hz.... Why?
The indicated value can be adjusted by the calibration parameter C4 Terminal 2 frequency setting gain
(Refer to Chapter 4 of
The frequency meter (indicator) connected across terminals FM and SD can be adjusted by the
calibration parameter C0 FM terminal calibration.
(Refer to Chapter 4 of
Set
frequency
at
parameter C2.
(Refer to Chapter 4 of
Manual (Applied).)
How can I operate at a frequency higher than
120Hz.
Additionally set Pr.18 High speed maximum
frequency.
(Refer to Chapter 4 of
Manual (Applied).)
REMARKS
As other adjustment methods of frequency setting voltage gain, there are methods to adjust with a voltage applied to across
terminals 2 and 5 and adjust at any point without a voltage applied.
(Refer to Chapter 4 of
the Instruction Manual (Applied) .)
68
to lit [EXT].
the Instruction Manual (Applied).)
the Instruction Manual (Applied).
Operation
(Pr. 125) appears.
". (50.00Hz)
the Instruction Manual (Applied).)
the Instruction Manual (Applied).)
0V
using
calibration
the Instruction
the Instruction
Display
···
Flicker
50Hz output at 5V input complete!!
Initial value
60Hz
Bias
C2
(Pr. 902)
0
0
Frequency setting signal
0
0
C3 (Pr. 902)
Pr.125
Gain
100%
5V
10V
20mA
C4 (Pr. 903)