Start and stop using terminals (External
operation)
3.4.6
Changing the output frequency (60Hz, initial value) at the maximum current input
(at 20mA, initial value)
<How to change the maximum frequency?>
Changing example
When you use the 4 to 20mA input and want to change the frequency at 20mA from 60Hz (initial
value) to 50Hz, set "50Hz" in Pr. 126.
Selecting the parameter number
Turn
until
1.
Press
to show the present set value. (60.00Hz)
Changing the maximum frequency
Turn
to change the set value to "
2.
Press
to set the value. "
Mode/monitor check
3.
Press
twice to choose the monitor/frequency monitor.
Start
4.
To check the setting, turn the start switch (STF or STR) ON and input 20mA. (Refer to 3.4.5 steps 2 and 3)
Set
frequency
at
parameter C5 and adjust the indicator using
calibration parameter C0.
(Refer to Chapter 4 of
(Applied).)
REMARKS
As other adjustment methods of frequency setting voltage gain, there are methods to adjust with a voltage applied across
terminals 4 and 5 or adjust at any point without a voltage applied.
(Refer to Chapter 4 of
92
(Pr. 126) appears.
" and "
4mA
using
calibration
the Instruction Manual
the Instruction Manual (Applied) for the setting method of calibration parameter C7.)
Operation
". (50.00Hz)
" flicker alternately.
60Hz
Bias
C5
(Pr. 904)
0
20
0
4
Frequency setting signal
0
1
0
2
C6 (Pr. 904)
Initial value
Pr. 126
Gain
100%
20mA
5V
10V
C7 (Pr. 905)