3. SPECIFICATIONS
MELSEC-A
3.
SPECIFICATIONS
This chapter describes general specifications, performance specifica-
tions, and cable specifications for the transmission converter.
-
3.1
General Specifications
General specifications for the transmission converter are indicated in
Table 3.1.
Table 3.1 General specifications
One octave marked
*
indicates a change from the lnltlal frequency to double or half frequency.
For example, any of the changes from lOHz to 20Hz, from 20Hz to 40Hz, from 40Hz to 20Hz,
and 20Hz to 10Hz are referred to as one octave.
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
,
humidity
.
~
Vibration resistance
Shock
resistance
Noise durability
Dielectric
withstand
voltage
Insulation resistance
Grounding
Operating amb~ence
Cooling method
**JIS: Japanese Industrial Standard
Specifications
0 to 500C(32 to 1310F)
-
-
-20 to 75"C(-4 to 167OF) -
-
10 to 90% RH, no condensation
10 to 90% RH, no condensation
Sweep Count
10 times
(1 octavelminute)
Conforms to JIS C 091 2 ( 9 8 m / ~ ~ [ l 0 ~ ] ,
3 times in 3 directions)
By noise simulator l500Vp-p noise voltage, l p s noise width, and 25 to 60Hz noise frequency
500V AC for 1 minute across batch of DC external terminals and ground
5 M n or larger by 5 0 0 ~ AC insulation reslstance tester across batch of AC external terminals
.and ground
Class 3 grounding; grounding is not requ~red when it is impossible.
To be free from corrosive gases, oil, and chemicals. Dust should be mlnimal.
Self-cooling
Amplitude
0.075mm(O.O031n)
Conforms to
**JIS
091
Frequency
10 to 5
5
~
~
55 to 150Hz
Acceleration
9.8m/s2{lg)
-
-