POFF(P)
Remark
Program Example
(1) The following program makes the program with the file name ABC non-executionable and
places it in the standby status when X0 is turned ON.
[Ladder Mode]
7-378
1. Non-execution processing is identical to the processing that is conducted when
the condition contacts for the individual coil instructions are in the OFF state.
The operation results for the individual coil instructions following non-execution
processing will be as follows, regardless of the ON/OFF status of the individual
contacts:
OUT instruction
SET instruction
RST instruction
SFT instruction
Basic instruction
Application instruction
PLS instruction
Pulse generation
instruction (
P)
Current value of low speed/high speed timer ...... 0
Current value of retentive timer
Current value of counter
...... Forced OFF
...... Maintains status
Processing identical to
......
when condition contacts
are OFF
...... Preserves
[List Mode]
Step
Instruction
Device