Error
Code
Error Contents and Cause
(SD0)
[OPERATION ERROR]
• The block data that crosses over the boundary
between the internal user device and the
extended data register (D) or extended link
register is specified (including 32-bit binary, real
number (single precision, double precision),
4101
indirect address, and control data).
■Collateral information
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[OPERATION ERROR]
In a multiple CPU system, the link direct device
(J \ ) was specified for the network module
under control of another station.
4102
■Collateral information
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[OPERATION ERROR]
• The network No. or station No. specified for the
dedicated instruction is wrong.
• The link direct device (J \ ) setting is incorrect.
• The module No./network No./number of
character strings exceeds the range that can be
specified.
■Collateral information
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[OPERATION ERROR]
• The module number specified with a dedicated
instruction is incorrect.
• The module number, network number, or the
4102
number of character strings specified with a
dedicated instruction exceeded the allowable
range.
■Collateral information
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[OPERATION ERROR]
The character string (" ") specified by a dedicated
instruction cannot be used for the character string.
■Collateral information
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[OPERATION ERROR]
The configuration of the PID dedicated instruction
is incorrect.
■Collateral information
4103
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[OPERATION ERROR]
PLOADP/PUNLOADP/PSWAPP instructions were
executed while setting program memory check.
■Collateral information
4105
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
Corrective Action
Read common information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value, and correct it as
necessary.
• Delete from the program the link direct device
which specifies the network module under
control of another CPU.
• Using the link direct device, specify the network
module controlled by the own station.
Read common information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value, and correct it as
necessary.
• Delete the setting for the program memory
check.
• When using the program memory check, delete
PLOADP/PUNLOADP/PSWAPP instructions.
LED Status
Corresponding
CPU Status
CPU
QnU
LCPU
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
*1
Continue
*8
Q00/Q01
*8
Qn(H)
QnPH
*18
QnU
QCPU
RUN:
Off/On
LCPU
ERR.:
Flicker/On
CPU Status:
Stop/
*1
Continue
QnU
LCPU
Q00J/Q00/Q01
Qn(H)
QnPRH
QnU
LCPU
RUN:
Off/On
ERR.:
*12
Flicker/On
QnPH
CPU Status:
Stop/Continue
12-61
1
2
3
12
6
6
7
8
*8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents