(13) Redundant system (other system CPU information
The special relay (SM1600 to SM1649) is valid when the redundant system is in backup mode and is invalid in
separate mode. All bits are set to off for stand-alone systems.
Number
Name
Other system
SM1600
error flag
Other system
SM1610
diagnostics error
Other systems
SM1611
self diagnostics
error.
Other system
SM1615
common error
information
Error individual
SM1626
information for
other systems
Standby system
SM1649
cancel error flag
*1
Stores other system CPU diagnostic information and system information.
*2
This shows the special relay (SM
App-180
Meaning
• This relay turns on if an error is detected by error
OFF : No error
check for redundant system. (This relay turns on
ON : Error
when any of the SD1600 bits turns on.)
• This relay turns off when an error is cleared.
• This relay turns on if a diagnostic error occurs in
the CPU module in the other system. (Also turns
OFF : No error
off when an annunciator turns on and when an
ON : Error
error is detected by the CHK instruction.)
• The SM0 status for the CPU module in the other
system is reflected.
• This relay turns on if a self-diagnostics error
OFF : No self
occurred in the CPU module in the other system.
diagnostics error
(Excluding error detections by an annunciator
occurred
and the CHK instruction.)
ON : Self diagnostics
• The SM1 status for the CPU module in the other
error occurred
system is reflected.
OFF : No common error
• This relay turns on when there is error common
information
information data for an error occurred in the
present
CPU module in the other system.
ON : Common error
• The SM5 status for the CPU module in the other
information
system is reflected.
present
OFF : No individual
• This relay turns on when there is error individual
error information
information for an error occurred in the CPU
present
module in the other system.
ON : Individual error
• The SM16 status for the CPU module in the
information
other system is reflected.
present
This relay is turned on from off to clear a
OFF to ON:
continuation error occurred in the standby system.
Cancels error of
Use SD1649 to specify the error code of the error
standby system
to be canceled.
) for the host system CPU.
*1
)
Explanation
Corres-
Set by
ponding
(When Set)
ACPU
*2
SM
-
SM0
SM1
S (Every END
processing)
SM5
SM16
U
-
Correspo
nding
CPU
QnPRH