Error
Code
Error Contents and Cause
(SD0)
[BLOCK EXE. ERROR]
Startup was executed at a block in the SFC
program that was already started up.
■Collateral information
4620
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[BLOCK EXE. ERROR]
Startup was attempted at a block that does not
exist in the SFC program.
■Collateral information
4621
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[STEP EXE. ERROR]
The step specified in the SFC program is already
activated.
■Collateral information
4630
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[STEP EXE. ERROR]
• Startup was attempted at the step that does not
exist in the SFC program.
Or, the step that does not exist in the SFC
program was specified for end.
• Forced transition was executed based on the
transition condition that does not exit in the SFC
program.
4631
Or, the transition condition for forced transition
that does not exit in the SFC program was
canceled.
■Collateral information
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[STEP EXE. ERROR]
There were too many simultaneous active steps in
blocks that can be designated by the SFC
program.
4632
■Collateral information
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
[STEP EXE. ERROR]
There were too many simultaneous active steps in
all blocks that can be designated.
■Collateral information
4633
• Common information: Program error location
• Individual information:-
■Diagnostic Timing
• When instruction executed
*1
CPU operations when an error occurred can be determined with a parameter. (LED indication varies according to the
CPU module status.)
*8
This applies if the function version is B or later.
*10
This applies when the first five digits of the serial number is "04101" or later.
*11
This applies when the first five digits of the serial number is "07012" or later.
*12
This applies when the first five digits of the serial number is "07032" or later.
*15
This applies when the first 5 digits of the serial No. is "09102" or later
*18
This applies to the Universal model QCPU except for the Q00UJCPU.
*19
This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, and Q01UCPU.
*20
This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
*21
This applies to the Built-in Ethernet port QCPU.
Corrective Action
Read common information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value, and correct it as
necessary.
• Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the error
step corresponding to the value, and correct it
as necessary.
• Turn on SM321 if it is off.
Read common information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value, and correct it as
necessary.
• Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the error
step corresponding to the value, and correct it
as necessary.
• Turn on SM321 if it is off.
Read common information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value, and correct it as
necessary.
LED Status
Corresponding
CPU Status
CPU
Qn(H)
QnPH
QnPRH
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
RUN:
Off
ERR.:
Qn(H)
Flicker
QnPH
QnPRH
CPU Status:
Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
RUN:
Off
Qn(H)
ERR.:
QnPH
Flicker
QnPRH
QnU
CPU Status:
LCPU
Stop
12-71
1
2
3
*8
12
6
6
7
8
*8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents