12.1.3

Error code list (1000 to 1999)

The following shows the error messages from the error code 1000 to 1999, the contents and
causes of the errors, and the corrective actions for the errors.
Error
Error Contents and Cause
Code
[MAIN CPU DOWN]
Runaway or failure of the CPU module
• Malfunctioning due to noise or other reason
• Hardware failure
■Collateral information
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• Always
1000
[CPU UNIT DOWN]
Runaway or failure of the CPU module
• Malfunctioning due to noise or other reason
• Hardware failure
■Collateral information
• Common Information:-
• Individual Information: Failure information
■Diagnostic Timing
• Always
[MAIN CPU DOWN]
Runaway or failure of the CPU module
• Malfunctioning due to noise or other reason
• Hardware failure
• The devices outside the range was accessed
even though device checks are prohibited
(SM237 is on). (This error occurs only when any
of the BMOV, FMOV, or DFMOV instructions is
executed. (Universal model QCPU only))
■Collateral information
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• Always
1001
[CPU UNIT DOWN]
Runaway or failure of the CPU module
• Malfunctioning due to noise or other reason
• Hardware failure
• The devices outside the range was accessed
even though device checks are prohibited
(SM237 is on). (This error occurs only when any
of the BMOV, FMOV, or DFMOV instruction is
executed.)
■Collateral information
• Common Information:-
• Individual Information: Failure information
■Diagnostic Timing
• Always
12-4
Corrective Action
• Take noise reduction measures.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a hardware failure of the CPU module. (Please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.)
• Take noise reduction measures.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a hardware failure of the CPU module. (Please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.)
• Check the devices specified by BMOV, FMOV,
and DFMOV instructions and correct the device
settings.
• (Universal model QCPU only)
• Take noise reduction measures.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a hardware failure of the CPU module. (Please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.)
• Check the devices specified by BMOV, FMOV,
or DFMOV instruction, and correct the device
settings.
LED Status
Corresponding
CPU Status
CPU
QCPU
LCPU
RUN:
Off
ERR.:
Flicker
CPU Status:
QCPU
Stop
LCPU