(15) Redundant power supply module information
Number
Name
Power supply off
SM1780
detection flag
Power supply
SM1781
failure detection
flag
Momentary power
failure detection
SM1782
flag for power
*1
supply 1
Momentary power
failure detection
SM1783
flag for power
*2
supply 2
*1: The "power supply 1" indicates the redundant power supply module mounted on the POWER 1 slot of the redundant base
unit (Q38RB/Q68RB/Q65WRB).
*2:The "power supply 2" indicates the redundant power supply module mounted on the POWER 2 slot of the redundant base
unit (Q38RB/Q68RB/Q65WRB).
*3:The module whose first 5 digits of serial No. is "04012" or later.
However, for the multiple CPU system configuration, this applies to all CPU modules whose first 5 digits of serial No. are
"07032" or later.
*4:The module whose first 5 digits of serial No. is "10042" or later.
App-184
Meaning
• Turns ON when one or more redundant
OFF : No redundant
power supply modules with input power
power supply
OFF are detected.
module with
• Turns on if any of SD1780 bits is on.
input power OFF
• Turns off if all bits of SD1780 are off.
detected
• This relay turns off when the main base
ON : Redundant
unit is not the redundant main base unit
power supply
(Q38RB).
module with
• When the multiple CPU system is
input power OFF
configured, the flags are stored only to the
detected
CPU No.1.
• Turns ON when one or more faulty
redundant power supply modules are
OFF : No faulty
detected.
redundant power
• Turns on if any of SD1781 bits is on.
supply module
• Turns off if all bits of SD1781 are off.
detected
• This relay turns off when the main base
ON : Faulty redundant
unit is not the redundant main base unit
power supply
(Q38RB).
module detected
• When the multiple CPU system is
configured, the flags are stored only to the
CPU No.1.
• Turns ON when a momentary power failure
of the input power supply to the power
supply 1 or 2 is detected one or more
times. After turning on, this relay remains
on even if the power supply recovers from
the momentary power failure.
OFF : No momentary
• Turns off the flags (SM1782 and SM1783)
power failure
of the power supply 1 and 2 when the CPU
detected
module starts.
ON : Momentary
• When the input power to one of the
power failure
redundant power supply modules turns
detected
OFF the corresponding flag turns OFF.
• This relay turns off when the main base
unit is not the redundant main base unit
(Q38RB).
• When the multiple CPU system is
configured, the flags are stored only to the
CPU No.1.
Explanation
Corres-
Set by
ponding
Corres-ponding
(When Set)
ACPU
M9
S (Every END
New
processing)
CPU
*3
Qn(H)
*3
QnPH
QnPRH
*4
QnU