Mitsubishi MELSEC Q Series Programming Manual page 971

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Error
Error Contents and Cause
Code
[LINK PARA. ERROR]
A CC-Link IE controller network parameter error
was detected.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
• The network module detected a network
parameter error.
• A MELSECNET/H network parameter error was
detected.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
The station No. specified in pairing setting are not
correct.
• The stations are not numbered consecutively.
• Pairing setting has not been made for the CPU
module at the normal station.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
The CC-Link IE controller network module whose
first 5 digits of serial No. is "09041" or earlier is
3102
mounted.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
Group cyclic function in CC-Link IE controller
network that does not correspond to group cyclic
function is set.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
Paring setting in CC-Link IE controller network
modules installed in CPUs except for redundant
CPUs was performed.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
• LB/LW own station send range at LB/LW4000 or
later was set.
• LB/LW setting (2) was performed.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
Corrective Action
• Correct and write the network parameters.
• If the error occurs after correction, it suggests a
hardware fault. (Please consult your local
Mitsubishi representative, explaining a detailed
description of the problem.)
Refer to the troubleshooting of the network
module, and if the error is due to incorrect pairing
setting, reexamine the pairing setting of the
network parameter.
Mount the CC-Link IE controller network module
whose first 5 digits of serial No. is "09042" or later.
Set group cyclic function in function version D or
later of CC-Link IE controller network.
Examine the paring setting for the network
parameter in the control station.
Correct the network range assignments of the
network parameter for the control station.
LED Status
Corresponding
CPU Status
CPU
*15
Qn(H)
*17
QnPH
*17
QnPRH
QnU
QCPU
QnPRH
RUN:
Off
ERR.:
Flicker
QnU
CPU Status:
Stop
*10
QnU
Q00J/Q00/Q01
*17
Qn(H)
*17
QnPH
*17
QnU
Q00J/Q00/Q01
12-51
1
2
3
12
6
6
7
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series