FDEL(P),FINS(P)
Program Example
(1) The following program deletes the second data from the table R0 to R7 and stores the
deleted data at D0 when X10 is turned ON.
[Ladder Mode]
[Operation]
Data table
range
(2) The following program inserts the data at D0 into the third position at the table R0 to R7
when X10 is turned ON.
[Ladder Mode]
[Operation]
Data table
range
7-158
Data table
R0
5
X10:ON
R1
-123
R2
4444
R3
3210
R4
1234
R5
5432
R6
0
R7
0
Data table
R0
4
X10:ON
R1
1234
R2
4444
R3
-123
R4
5000
R5
0
R6
0
R7
0
D0
-3210
[List Mode]
Step
Instruction
Data table
R0
4
R1
-123
R2
3210
Data table
range
R3
1234
R4
5432
R5
0
R6
0
R7
0
D0
4444
[List Mode]
Step
Instruction
Data table
R0
5
R1
1234
R2
4444
R3
-3210
R4
-123
R5
5000
R6
0
R7
0
Device