Error
Error Contents and Cause
Code
[MAIN CPU DOWN]
Runaway or failure of the CPU module
• Malfunction due to noise etc.
• Hardware failure
■Collateral information
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• Always
1035
[CPU UNIT DOWN]
Runaway or failure of the CPU module
• Malfunction due to noise etc.
• Hardware failure
■Collateral information
• Common Information:-
• Individual Information: Failure information
• Diagnostic Timing
• Always
1040
[CPU UNIT DOWN]
Runaway or failure of the CPU module (built-in I/
1041
O).
• Malfunction due to noise etc.
• Hardware failure
■Collateral information
1042
• Common Information:-
• Individual Information: Failure information
■Diagnostic Timing
• Always
[RAM ERROR]
The sequence program storing program memory
in the CPU module is faulty.
■Collateral information
• Common Information:-
1101
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset/When an END instruction
executed
[RAM ERROR]
• The work area RAM in the CPU module is
faulty.
• The standard RAM in the CPU module is faulty.
■Collateral information
1102
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset/When an END instruction
executed
[RAM ERROR]
The device memory in the CPU module is faulty.
■Collateral information
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset/When an END instruction
executed
[RAM ERROR]
1103
• The device memory in the CPU module is faulty.
• The device out of range is accessed due to
indexing, and the device for system is
overwritten.
■Collateral information
• Common Information:-
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/When an END instruction
executed
12-8
Corrective Action
• Take noise reduction measures.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a failure of the CPU module. (Please consult
your local Mitsubishi representative, explaining
a detailed description of the problem.)
• Take noise reduction measures.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a failure of the CPU module. (Please consult
your local Mitsubishi representative, explaining
a detailed description of the problem.)
• Take noise reduction measures.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a hardware failure of the a CPU module.
(Please consult your local Mitsubishi
representative, explaining a detailed description
of the problem.)
• Take noise reduction measures.
• When indexing is performed, check the value of
index register to see if it is within the device
range.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a hardware failure of the a CPU module.
(Please consult your local Mitsubishi
representative, explaining a detailed description
of the problem.)
LED Status
Corresponding
CPU Status
CPU
QnU
LCPU
RUN:
Off
ERR.:
LCPU
Flicker
CPU Status:
Stop
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU
RUN:
Off
ERR.:
Flicker
CPU Status:
*13
Qn(H)
Stop
*13
QnPH
QnPRH
*15