Error
Error Contents and Cause
Code
[LINK PARA. ERROR]
• The CC-Link parameter setting is incorrect.
• The set mode is not allowed for the version of
the mounted CC-Link module.
3107
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[SFC PARA. ERROR]
The parameter setting is illegal.
• The block 0 does not exist although "Autostart
Block 0" was selected in the SFC tab in the PLC
Parameter dialog box.
3200
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• STOP→RUN
[SFC PARA. ERROR]
The block parameter setting is illegal.
■Collateral information
• Common information: File name
3201
• Individual information: Parameter number
■Diagnostic Timing
• STOP→RUN
[SFC PARA. ERROR]
The number of step relays specified in the device
setting of the PLC parameter dialog box is less
than that used in the program.
3202
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• STOP→RUN
[SFC PARA. ERROR]
For the execution type of the SFC program, other
than "Scan" is selected in the Program tab of the
PLC Parameter dialog box.
■Collateral information
3203
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[SP. PARA ERROR]
The start I/O number in the intelligent function
module parameter set on GX Configurator differs
from the actual I/O number.
■Collateral information
3300
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
12-54
Corrective Action
Check the parameter setting.
Read common information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value, and correct it as
necessary.
*5
Check the parameter setting.
*4
LED Status
Corresponding
CPU Status
CPU
QCPU
LCPU
Q00J/Q00/Q01
QnPH
QnPRH
QnU
LCPU
RUN:
Off
Qn(H)
ERR.:
QnPH
Flicker
QnPRH
CPU Status:
Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
QCPU
LCPU
*8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents