Mitsubishi MELSEC Q Series Programming Manual page 553

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(a) The device numbers indicated at check conditions (X2 and X8 in the figure below) will
assume index modification values for the individual device numbers (with the exception
of annunciators (F)) described in the ladder patterns.
Example
X10 in the
When corresponding to check condition X2 Processing performed by ...X12
When corresponding to check condition X8 Processing performed by ...X18
However, the order in which failure detection is executed differs depending on whether
SM710 is ON or OFF.
1) If SM710 is OFF, checks will be conducted of coil numbers 1 through the end for
each contact successively.
[Ladder designated by CHKCIR to CHKEND]
X2
X8
SM400
X10Z0 X12Z0 Y40Z0 X6Z0
X8Z0
Y5EZ0 X21Z0 Y46Z0 X1AZ0
Y5FZ0 X22Z0
SM400
2) If SM710 is ON, checks will be conducted of contact numbers 1 through the end, in
coil number order.
[Ladder designated by CHKCIR to CHKEND]
X2
X8
SM400
X10Z0 X12Z0 Y40Z0 X6Z0
X8Z0
Y5EZ0 X21 Z0 Y46Z0 X1AZ0
Y5FZ0 X22Z0
SM400
in the figure below would be as follows:
[Order of check by CPU module]
X12 X14
Y42 X8
CHKST
XA
CHK
Y60 X23
Y48 X1C
CHKCIR
Y61 X24
F0
X18 X1A
Y48 XE
F1
X10
F2
Y66 X29 Y4E X22
Y67 X2A
CHKEND
[Order of check by CPU module]
X12 X14
CHKST
X18 X1A
CHK
X12 X14
CHKCIR
Y18 X1A
F0
Y60 X23 Y48 X1C
F1
X61 X24
F2
Y66 X29 Y4E X22
Y67 X2A
CHKEND
CHKCIR,CHKEND
F0
F1
Ladder
equivalent to X2
F2
F0
F1
Ladder
equivalent to X8
F2
Y42 X8
F0
Y48 XE
F0
XA
F1
X10
F1
F2
F2
1
2
3
4
6
6
7
8
7-179

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents