Mitsubishi MELSEC Q Series Programming Manual page 948

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Error
Error Contents and Cause
Code
[SP. UNIT ERROR]
• The module other than intelligent function
module/special function module is specified by
the intelligent function module/special function
module dedicated instruction. Or, it is not the
corresponding intelligent function module/
special function module.
• There is no network No. specified by the
network dedicated instruction. Or the relay
target network does not exit.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic Timing
2112
• When instruction executed/STOP→RUN
[SP. UNIT ERROR]
• The module other than intelligent function
module was specified with an intelligent function
module dedicated instruction. Or there is no
relevant intelligent function module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic Timing
• When instruction executed/STOP→RUN
[SP. UNIT ERROR]
The module other than network module is
specified by the network dedicated instruction.
■Collateral information
2113
• Common information: FFFF
• Individual information: Program error location
■Diagnostic Timing
• When instruction executed/STOP→RUN
[SP. UNIT ERROR]
An instruction, which on execution specifies other
stations, has been used for specifying the host
CPU. (An instruction that does not allow the host
CPU to be specified).
2114
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic Timing
• When instruction executed/STOP→RUN
[SP. UNIT ERROR]
An instruction, which on execution specifies the
host CPU, has been used for specifying other
CPUs. (An instruction that does not allow other
stations to be specified).
2115
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic Timing
• When instruction executed/STOP→RUN
[SP. UNIT ERROR]
• An instruction that does not allow the under the
control of another CPU to be specified is being
used for a similar task.
• Instruction was executed for the A or QnA
2116
module under control of another CPU.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic Timing
• When instruction executed/STOP→RUN
12-28
Read the individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
intelligent function module/special function
module dedicated instruction (instruction for a
network) corresponding to the value and correct it
as necessary.
• Read the individual information of the error
using the programming tool to identify the
numeric value (program error location). Check
the intelligent function module dedicated
instruction corresponding to the value and
correct it as necessary.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause
is a hardware failure of the CPU module, I/O
module, intelligent function module, or END
cover. (Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.)
Read the individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
intelligent function module/special function
(fixed)
H
module dedicated instruction (instruction for a
network) corresponding to the value and correct it
as necessary.
Read individual information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value and correct it as
necessary.
Corrective Action
LED Status
Corresponding
CPU Status
CPU
QCPU
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
*1
Continue
LCPU
RUN:
Off/On
ERR.:
Flicker/On
Qn(H)
QnPH
CPU Status:
Stop/
*1
Continue
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
RUN:
Off/On
Q00J/Q00/Q01
ERR.:
Qn(H)
Flicker/On
QnPH
CPU Status:
Stop/Continue
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
*8
*8
*8
*8
*8
*8

Hide quick links: