Error
Error Contents and Cause
Code
[CAN'T EXE. PRG.]
The program file is incorrect.
Or the contents of the file are not programs.
■Collateral information
• Common information: File name/Drive name
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
2502
[CAN'T EXE. PRG.]
The program file is not the one for the redundant
CPU.
■Collateral information
• Common information: File name/Drive name
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[CAN'T EXE. PRG.]
There are no program files at all.
■Collateral information
• Common information: File name/Drive name
2503
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[CAN'T EXE. PRG.]
Two or more SFC normal programs or control
programs have been designated.
■Collateral information
• Common information: File name/Drive name
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
2504
[CAN'T EXE. PRG.]
There are two or more SFC programs.
■Collateral information
• Common information: File name/Drive name
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[REMOTE PASS.FAIL]
The count of remote password mismatches
reached the upper limit.
■Collateral information
2700
• Common information:-
• Individual information:-
■Diagnostic Timing
• Always
[SNTP OPE.ERROR]
Time setting failed when the programmable
controller was powered ON or reset.
■Collateral information
2710
• Common information:-
• Individual information:-
■Diagnostic Timing
• When time setting function is executed
12-40
Corrective Action
Ensure that the program version is ***.QPG and
the file contents are programs.
Create a program with GX Developer or PX
Developer specifying the redundant CPU
(Q12PRH/Q25PRH) as the PLC type, and write it
to the CPU module.
• Check program configuration.
• Check parameters and program configuration.
• Check program configuration.
• Check parameters and program configuration.
Reduce the SFC programs to one.
Check for illegal accesses. If any illegal access is
identified, take actions such as disabling
communication of the connection.
If it was identified not illegal, clear the error and
perform the following. (Clearing the error also
clears the remote password mismatch counts.)
• Check if the remote password sent is correct.
• Check if the remote password has been locked.
• Check if concurrent access was made from
multiple devices to one connection by UDP.
• Check if the upper limit of the remote password
mismatch count is too low.
• Check if the time setting function is set up
correctly.
• Check if the specified SNTP server is operating
normally, or if any failure has occurred on the
network connected to the specified SNTP
server computer.
LED Status
Corresponding
CPU Status
CPU
QCPU
LCPU
QnPRH
RUN:
Off
ERR.:
Flicker
QCPU
LCPU
CPU Status:
Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
Q00J/Q00/Q01
RUN:
On
ERR.:
On
CPU Status:
Continue
*21
QnU
LCPU
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
*1
Continue
*8