Error
Error Contents and Cause
Code
[CONTROL-BUS. ERR.]
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
■Collateral information
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• Always
1413
[CONTROL-BUS. ERR.]
An error is detected on the system bus.
• Self-diagnosis error of the system bus.
• Self-diagnosis error of the CPU module
■Collateral information
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• Always
[CONTROL-BUS. ERR.]
• Fault of a loaded module was detected.
• In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
■Collateral information
• Common Information: Module No. (Slot No.)
• Individual Information:-
■Diagnostic Timing
1414
• Always
[CONTROL-BUS. ERR.]
An error is detected on the system bus.
■Collateral information
• Common Information: Module No. (Slot No.)
• Individual Information:-
■Diagnostic Timing
• Always
[CONTROL-BUS. ERR.]
Fault of the main or extension base unit was
detected.
■Collateral information
• Common Information: Module No. (Slot No.)
• Individual Information:-
■Diagnostic Timing
• When an END instruction executed
1415
[CONTROL-BUS. ERR.]
Fault of the main or extension base unit was
detected.
■Collateral information
• Common Information: Module No. (Slot No.)
• Individual Information:-
■Diagnostic Timing
• At power-ON/At reset/When an END instruction
executed
12-16
Corrective Action
• Remove the CPU module from the main base
unit if it does not support a multiple CPU system
configuration. Alternatively, replace the CPU
module that does not support a multiple system
configuration with the one that does.
• The cause is a failure of the intelligent function
module, CPU module, or base unit. (Please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.)
Reset the CPU module and run it again. If the
same error code is displayed again, the cause is a
failure of the intelligent function module, CPU
module, or base unit. (Please consult your local
Mitsubishi representative, explaining a detailed
description of the problem.)
• Remove the CPU module from the main base
unit if it does not support the multiple CPU
system configuration. Or replace the CPU
module that does not support a multiple system
configuration with the one that does. Reset the
CPU module and run it again. If the same error
code is displayed again, the cause is a failure of
the intelligent function module, CPU module, or
base unit. (Please consult your local Mitsubishi
representative, explaining a detailed description
of the problem.)
Reset the CPU module and run it again. If the
same error code is displayed again, the cause is a
failure of the intelligent function module, CPU
module, or base unit.
(Please consult your local Mitsubishi
representative, explaining a detailed description of
the problem.)
LED Status
Corresponding
CPU Status
CPU
Q00J/Q00/Q01
*8
Qn(H)
QnPH
QCPU
Q00J/Q00/Q01
RUN:
*8
Qn(H)
Off
QnPH
ERR.:
QnU
Flicker
CPU Status:
Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
Q00J/Q00/Q01
*8
Qn(H)
QnPH
QnPRH
QnU
*13
Qn(H)
*13
QnPH
*8
*8
*8