JMP
(1) Unconditionally executes program of designated pointer number within the same program
file.
Note the following points when using the jump instruction.
1. After the timer coil has gone ON, accurate measurements cannot be made if
there is an attempt to jump the timer of a coil that has been turned ON using the
CJ, SCJ or JMP instructions.
2. Scan time is shortened if the CJ, SCJ or JMP instruction is used to force a jump
to the OUT instruction.
3. Scan time is shortened if the CJ, SCJ or JMP instruction is used to force a jump
to the rear.
4. The CJ, SCJ, and JMP instructions can be used to jump to a step prior to the
step currently being executed. However, it is necessary to consider methods to
get out of the loop so that the watchdog timer does not time out in the process.
When X3 is
ON, the loop
is closed.
5. The device to which a jump has been made with the CJ, SCJ or JMP does not
change.
6. The label (P*) occupies step 1.
Occupies 1 step
7. The jump instructions can be used only for pointer numbers within the same
program file.
8. If a jump is made to a pointer number inside the skip range during a skip
operation, program execution will be taken up following the pointer number of
the jump destination.
X0
P8
X7
X3
P9
X6
XB
10
XC
14
XB
16
P19
X9
18
X8
10
M33
14
M3
16
P9
M36
18
X9
21
Y40
CJ
P9
Exits the loop when
CJ
P8
X7 is turned ON.
Y42
Jumps to label P19
CJ
P19
when XB turns ON.
Y43 and Y49 remain
unchanged regardless
Y43
of whether XB and XC are
turned ON/OFF during the
Y49
execution of CJ instruction.
Y4C
CJ
P9
Y30
Y36
Y39
Y3B
CJ,SCJ,JMP
1
2
3
4
4
6
7
8
6-133

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents