Mitsubishi MELSEC Q Series Programming Manual page 1204

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(1) Diagnostic information
Number
Name
Diagnostic
Diagnosis error
SD0
errors
code
SD1
Clock time for
Clock time for
SD2
diagnosis error
diagnosis error
occurrence
occurrence
SD3
App-196
Meaning
• This register stores the error code of an error detected by
diagnostics.
• Contents identical to latest fault history information.
This register stores the year (last two digits) and the month
when the SD0 data is updated in 4-digit BCD.
b15
to
Year (0 to 99) Month (1 to 12)
This register stores the day and the hour when the SD0 data is
updated in 4-digit BCD.
b15
to
b8
Day (1 to 31) Hour (0 to 23)
This register stores the minute and the second when the SD0
data is updated in 4-digit BCD.
b15
to
Minutes (0 to 59) Seconds (0 to 59)
Explanation
(Example) October, 1995
b8
b7
to
b0
(Example) 10 a.m. on 25th
b7
to
b0
(Example) 35 min. 48 sec.
b8
b7
to
b0
Set by
(When Set)
9510
H
S
(Error)
2510
H
3548
H
Corres-
Corres-
ponding
ponding
ACPU
CPU
D9
D9008
format
change
QCPU
LCPU
New

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents