Error
Error Contents and Cause
Code
[SP. PARA ERROR]
• The refresh setting of the intelligent function
module exceeded the file register capacity.
• The intelligent function module set in GX
Configurator differs from the actually mounted
module.
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
The intelligent function module's refresh parameter
setting is outside the available range.
■Collateral information
3301
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
The setting of the refresh parameter range crosses
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
The intelligent function module's refresh parameter
are abnormal.
■Collateral information
• Common information: File name
3302
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to the
intelligent function module under control of another
station.
3303
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
Corrective Action
• Change the file register file for the one which
allows refresh in the whole range.
• Check the parameter setting.
• Check the auto refresh setting.
*4
• Check the parameter setting.
• Check the auto refresh setting.
*4
Set the refresh parameter range so that it does
not cross over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
*4
Check the parameter setting.
*4
• Delete the automatic refresh setting or other
parameter setting of the intelligent function
module under control of another CPU.
• Change the setting to the automatic refresh
setting or other parameter setting of the
intelligent function module under control of the
host CPU.
LED Status
Corresponding
CPU Status
CPU
Q00J/Q00/Q01
*8
Qn(H)
QnPH
QnPRH
QnU
LCPU
QCPU
LCPU
RUN:
Off
ERR.:
Flicker
QnU
LCPU
CPU Status:
Stop
QCPU
LCPU
*8
Q00/Q01
*8
Qn(H)
QnPH
*18
QnU
12-55
1
2
3
12
6
6
7
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents