Error
Error Contents and Cause
Code
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is set to other than 0
■Collateral information
• Common information:-
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is set to other than 0
■Collateral information
• Common information:-
• Individual information:-
3400
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[REMOTE PASS. ERR.]
For the start I/O number of the module targeted by
the remote password, the value outside the
following range is specified.
Q00JCPU: 0
to 1E0
H
Q00CPU/Q01CPU: 0
■Collateral information
• Common information:-
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[REMOTE PASS. ERR.]
Position specified as the head I/O number of the
remote password file is incorrect due to one of the
following reasons:
• Module is not loaded.
• Other than a the intelligent function module (I/O
module)
• The intelligent function module installed is other
than a serial communication module, modem
interface module, or Ethernet module.
• The function version of the serial communication
module and Ethernet module installed is A.
• The intelligent function module where remote
password is available is not mounted.
■Collateral information
• Common information:-
3401
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[REMOTE PASS. ERR.]
The position specified with the start I/O number of
the remote password is invalid due to one of the
following reasons:
• No module
• The intelligent function module installed is other
than a serial communication module.
■Collateral information
• Common information:-
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
12-56
to 0FF0
.
H
H
Change the head I/O number of the target module
to be within the 0
to 07E0
.
H
H
Change the head I/O number of the target module
to be within the 0
Correct the start I/O number value of the module
targeted by the remote password within the
H
following range.
to 3E0
H
H
Install the serial communication module, modem
interface module, or Ethernet module of function
version B or later in the position specified with the
start I/O No. of the remote password.
In a position specified with a start I/O number of
the remote password, install the intelligent
function module where the remote password is
available.
Corrective Action
to 0FF0
range.
H
H
to 07E0
range.
H
H
• Q00JCPU: 0
to 1E0
H
H
• Q00CPU/Q01CPU: 0
to 3E0
H
H
LED Status
Corresponding
CPU Status
CPU
Qn(H)
QnPH
QnPRH
*15
QnU
LCPU
Q02UCPU
Q00J/Q00/Q01
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
*8
*8
*8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series

Table of Contents