(6) Designating "Un" in the argument enables the target designation of the intelligent function as
well as the network modules.
In this case, the auto refresh is performed for the buffer memory of the intelligent function
modules. (It replaces the FROM/TO instructions.)
(7) Only with the Universal model QCPU and LCPU, interruption of processing is enabled
during the execution of the ZCOM instruction. However, when refresh data are used in an
interrupted program, the data can split.
1. The ZCOM instruction cannot be used in a fixed cycle execution type program
2. The Redundant CPU has restrictions on use of the ZCOM instruction.
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
• When the specified network number is not connected to the host station
• When the module specified with the head I/O number is not a network module or link
module (Basic model QCPU, High Performance model QCPU, Process CPU, and
Redundant CPU)
• When the module specified with the head I/O number is not a network module or link
module (Universal model QCPU, LCPU)
To conduct only communication with peripheral device, use the COM instruction
(refer to Section 7.6.9, 9.1).
Program Example
(1) The following program conducts a link refresh for the network module of network No. 6 while
X0 is ON.
[Ladder Mode]
(2) The following program conducts a link refresh for the network module mounted to the
position whose head I/O number is a X/Y30 to X/Y4F while X0 is ON.
[Ladder Mode]
or interrupt program.
Refer to the manual below for details.
• QnPRHCPU User's Manual (Redundant System)
[List Mode]
Step
Instruction
[List Mode]
Step
Instruction
ZCOM
(Error code: 4102)
(Error code: 2111)
(Error code: 4102)
Device