Stopping Methods

This section explains methods of stopping the Drive.

Selecting the Stopping Method when a Stop Command is Sent

There are four methods of stopping the Drive when a stop command is sent:
Deceleration to stop
Coast to stop
DC braking stop
Coast to stop with timer
Set parameter b1-03 to select the Drive stopping method. A DC braking stop and coasting to a stop with a
timer cannot be set for flux vector control.
Related Parameters
Name
Parameter
Number
Display
Stopping
Selects the stopping method when the
Method
run command is removed.
Selection
0: Ramp to Stop
1: Coast to Stop
b1-03
2: DC Injection to Stop
Stopping
3: Coast with Timer (A new run
Method
Minimum
Operation method when frequency
Output
reference is less than minimum output
Frequency
frequency set in E1-09.
(E1-09) or
0: Operates according to frequency
Less
b1-05
Operation
1: Output shuts off (coast to stop if less
Selection
2: Operates according to E1-09
Zero-Speed
3: Zero speed (frequency reference
Oper
DC
Sets the frequency at which DC injection
Injection
braking starts when ramp to stop
Braking
(b1-03 = 0) is selected. If b2-01< E1-09,
Start
b2-01
DC Injection braking starts at E1-09.
Frequency
Note: Zero Speed restrictions are active
DCInj Start
in Flux Vector Mode.
Freq
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
command is ignored if received
before the timer expires).
reference (E1-09 is disabled).
than E1-09).
(frequency reference set to E1-09).
becomes zero when less than E1-09).
Change
Setting
Factory
during
Range
Setting
V/f
Operation
*
0
No
Q
0 to 3
0 to 3
0
No
No
0.0 to
0.5Hz
No
A
10.0
Stopping Methods
Control Methods
Open-
Open
V/f
Loop
Flux
Loop
with
Vector
Vector
Vector
PG
1
2
Q
Q
Q
Q
No
No
A
No
A
A
A
A
9
6-