YASKAWA G7 Series Technical Manual page 131

Table of Contents

Advertisement

Name
Parameter
Description
Number
Display
PID
Feedback Loss
Sets the PID feedback loss
Detection
detection level as a
b5-13
Level
percentage (%) of maximum
frequency (E1-04).
Fb los Det
Lvl
PID
Feedback
Loss
Sets the PID feedback loss
Detection
b5-14
detection delay time in terms
Time
of seconds.
Fb los Det
Time
PID Sleep
Sets the sleep function start
Function
frequency.
Start level
b5-15
Note: Enabled even when
PID control mode has
PID Sleep
not been selected.
Level
PID Sleep
Delay Time
Sets the sleep function delay
b5-16
time in terms of 0.1 seconds.
PID Sleep
Time
PID
Applies an accel/decel time to
Accel/decel
the PID setpoint reference. The
Time
Drive's standard softstarter
b5-17
(C1-xx and S-curve) still
PID Acc/Dec
affects the output of the PID
Time
algorithm.
PID
Allows the b5-19 setting to be
Setpoint
the PID target setpoint value.
Selection
b5-18
0: Disabled
PID
1: Enabled
Setpoint Sel
PID Setpoint
Sets the PID target value.
b5-19
Use only when b5-18 = 1
PID Setpoint
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Control Methods
Change
Setting
Factory
V/f
during
Range
Setting
V/f
with
Operation
PG
0
to
0%
No
A
100
0.0
to
1.0 s
No
A
25.5
0.0
to
0.0Hz
No
A
400.0
0.0
to
0.0 s
No
A
25.5
0.0
to
0.0 s
No
A
25.5
0 to 1
0
No
A
0.0
to
0.0 %
No
A
100.0
User Parameter Tables
Open
Open
MODBUS
Loop
Flux
Loop
Register
Vector
Vector
Vector
1
2
A
A
A
A
1B1H
A
A
A
A
1B2H
A
A
A
A
1B3H
A
A
A
A
1B4H
A
A
A
A
1B5H
A
A
A
A
1DCH
A
A
A
A
1DDH
19
5-