Specifications
50Hz
60Hz Saturation
50Hz Saturation
72Hz
Variable
Torque 1
50Hz
Variable
Torque 2
Variable
Torque 1
60Hz
Variable
Torque 2
If one of the custom V/f patterns is selected, then parameters E1-04 through E1-13 will determine the V/f pattern.
When a factory Initialization is performed, the setting of E1-03 is unaffected but the settings of E1-04
IMPORTANT
through E1-13 are returned to their factory default settings.
Setting Precautions
When the setting is to user-defined V/f pattern, beware of the following points.
When changing control method, parameters E1-07 to E1-10 will change to the factory settings for that
control method.
Be sure to set the four frequencies as follows:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 8 Preset V/f Patterns
E1-03
V/f Pattern *1
(V)
230
0
0
17
10
(Hz)
0 1.3 2.5
50
(V)
1
230
F
2
1
F
2
17
10
(Hz)
0 1.5 3.0
50 60
(V)
230
3
3
17
10
(Hz)
0 1.5 3.0
60 72
(V)
4
230
5
57
4
40
5
10
9
(Hz)
0 1.3
25
50
(V)
6
230
7
57
6
40
7
10
9
(Hz)
0 1.5
30
60
Fig 6.63 User-Set V/f Pattern
Specifications
E1-03
V/f Pattern *1
High
230
Starting
8
Torque 1
50Hz
High
Starting
9
Torque 2
High
Starting
A
230
Torque 1
60Hz
High
28
22
Starting
B
17
13
Torque 2
(V)
230
90Hz
C
17
10
0 1.5 3.0
(V)
230
120Hz
D
17
10
0 1.5 3.0
(V)
230
180Hz
E
17
10
0 1.5 3.0
Individual Functions
(V)
9
8
28
22
15
13
(Hz)
0 1.3 2.5
50
(V)
B
A
(Hz)
0 1.5 3.0
60
C
(Hz)
60 90
D
(Hz)
60 120
E
(Hz)
60 180
6-
119

Advertisement

Table of Contents

Troubleshooting