YASKAWA G7 Series Technical Manual page 141

Table of Contents

Advertisement

Name
Parameter
Number
Display
Frequency
Frequency reference when
Reference 10
multi-function input
d1-10
"Multi-step speed reference 1, 4"
is ON. Setting units are
Reference 10
affected by o1-03.
Frequency
Frequency reference when
Reference 11
multi-function input
d1-11
"Multi-step speed reference 2, 4"
is ON. Setting units are
Reference 11
affected by o1-03.
Frequency
Frequency reference when
Reference 12
multi-function input
d1-12
"Multi-step speed reference 1, 2, 4"
is ON. Setting units are
Reference 12
affected by o1-03.
Frequency
Frequency reference when
Reference 13
multi-function input
d1-13
"Multi-step speed reference 3, 4"
is ON. Setting units are
Reference 13
affected by o1-03.
Frequency
Frequency reference when
Reference 14
multi-function input
d1-14
"Multi-step speed reference 1, 3, 4"
is ON. Setting units are
Reference 14
affected by o1-03.
Frequency
Frequency reference when
Reference 15
multi-function input
d1-15
"Multi-step speed reference 2, 3, 4"
is ON. Setting units are
Reference 15
affected by o1-03.
Frequency
Frequency reference when
Reference 16
multi-function input
d1-16
"Multi-step speed reference 1, 2, 3, 4"
is ON. Setting units are
Reference 16
affected by o1-03.
Jog
Frequency reference when:
Frequency
"Jog frequency reference" is
Reference
selected via multi-function
input terminals. "Jog
frequency reference" has
priority over "multi-step
speed reference 1 to 4".
d1-17
Parameter d1-17 is also the
Jog
reference for the JOG key on
Reference
the Digital Operator, and the
multi-function inputs
"forward jog" and "reverse
jog". Setting units are
affected by o1-03.
Note The unit is set in o1-03 (frequency units of reference setting and monitor). The default for o1-03 is 0 (increments of 0.01Hz).
* Setting range changes to 0 thru 66.0 when operating in Vector 2 wo/PG. The upper limit for the setting range also depends on the upper limit in E1-04. The
max setting is 400.00.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting
Factory
Description
Range
Setting
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0
to
400.00
*
0.00Hz
0.00Hz
6.00Hz
User Parameter Tables
Control Methods
Change
Open
V/f
during
Loop
Flux
V/f
with
Operation
Vector
Vector
PG
1
Yes
A
A
A
A
Yes
A
A
A
A
Yes
A
A
A
A
Yes
A
A
A
A
Yes
A
A
A
A
Yes
A
A
A
A
Yes
A
A
A
A
Yes
Q
Q
Q
Q
Open
MODBUS
Loop
Register
Vector
2
A
28BH
A
28CH
A
28DH
A
28EH
A
28FH
A
290H
A
291H
Q
292H
29