Acceleration and Deceleration Characteristics

This section explains the acceleration and deceleration characteristics of the Drive.

Setting Acceleration and Deceleration Times

Acceleration time indicates the time taken for the output frequency to climb from 0% to 100%. Deceleration
time indicates the time taken for the output frequency to reduce to 0%. The factory setting of the acceleration
time is C1-01, and the factory setting of the deceleration time is C1-02.
Related Parameters
Name
Parameter
Number
Display
Acceleration
Time 1
C1-01
Accel Time 1
Deceleration
Time 1
C1-02
Decel Time 1
Acceleration
Time 2
C1-03
Accel Time 2
Deceleration
Time 2
C1-04
Decel Time 2
Acceleration
Time 3
C1-05
Accel Time 3
Deceleration
Time 3
C1-06
Decel Time 3
Acceleration
Time 4
C1-07
Accel Time 4
Deceleration
Time 4
C1-08
Decel Time 4
Accel/Decel
Time Setting
C1-10
Units
Acc/Dec Units
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Sets the time to accelerate from
zero to maximum frequency.
Sets the time to decelerate from
maximum frequency to zero.
Sets the time to accelerate from
zero to maximum frequency when
selected via a multi-function
input.
Sets the time to decelerate from
maximum frequency to zero when
selected via a multi-function
input.
Sets the time to accelerate from
zero to maximum frequency when
selected via a multi-function
input.
Sets the time to decelerate from
maximum frequency to zero when
selected via a multi-function
input.
Sets the time to accelerate from
zero to maximum frequency when
selected via a multi-function
input.
Sets the time to decelerate from
maximum frequency to zero when
selected via a multi-function
input.
Sets the setting resolution of
C1-01 to C1-09
0: 0.01sec (0.00 to 600.00sec)
1: 0.1sec (0.0 to 6000.0sec)
Acceleration and Deceleration Characteristics
Change
Setting
Factory
during
Range
Setting
V/f
Operation
Yes
Q
Yes
Q
Yes
A
Yes
A
0.0 to
10.0sec
*
6000.0
No
A
No
A
No
A
No
A
0 or 1
1
No
A
Control Methods
Open
Open
V/f
Loop
Flux
Loop
with
Vector
Vector
Vector
PG
1
2
Q
Q
Q
Q
Q
Q
Q
Q
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
15