Name
Parameter
Description
Number
Display
Stall
Selects the stall prevention
Prevention
method to use to prevent Drive
Selection
faults during run.
During
0: Disabled - Drive runs a set
Running
frequency. A heavy load
may cause the Drive to trip
on an OC or OL fault.
1: Decel Time 1 - In order to
avoid stalling during heavy
loading, the Drive will
decelerate at Decel time 1
(C1-02) if the output current
exceeds the level set by
L3-05
L3-06. Once the current
level drops below the L3-06
level, the Drive will
StallP Run
accelerate back to its
Sel
frequency reference at the
active acceleration rate.
2: Decel Time 2 - Same as
setting 1 except the Drive
decelerates at Decel Time 2
(C1-04).
When output frequency is 6Hz
or less, stall prevention during
run is disabled regardless of
the setting in L3-05.
Stall
This parameter is enabled when
Prevention
L3-05 is set to "1" or "2". Drive
Level
rated current is set as 100%.
During
L3-06
Decrease the set value if
Running
stalling or excessive current
StallP Run
occurs with the factory settings.
Level
OV
Enables or disables OV
Suppression
suppression function, which
Function
allows the Drive to change the
Selection
output frequency as the load
L3-11
changes, to prevent an OV
fault.
OV Inhibit
0: Disabled
Sel
1: Enabled
OV
Sets the DC bus voltage level at
Suppression
which the OV suppression
Function
function is active.
Voltage
Normally, this setting does not
L3-12
Level
require adjustment. Decrease
the value if overvoltage occurs
OV Inhbt
even when OV suppression is
VoltLvl
enabled.
* In Flux Vector or in Open Loop Vector 2, the setting range becomes 0 to 2.
* *1 Values shown here are for 208-240V drives. Double the value when working with 380-480V drives.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Control Methods
Change
Setting
Factory
V/f
during
Range
Setting
V/f
with
Operation
PG
0 to 2
1
No
A
A
30
to
160%
No
A
A
200
0 to 1
0
No
No
No
350
to
380V
No
No
No
390
*1
*1
User Parameter Tables