Installation Orientation and Space

Install the Drive vertically so as not to reduce the cooling effect. When installing the Drive, always pro-
vide the following installation space to allow normal heat dissipation.
1.97in * (50mm) minimum
1.2in
(30.5mm) minimum
1.97in (50mm) minimum
Horizontal Clearance
* For Drive model G7U4300, this clearance dimension is 11.81in (300mm) minimum. All other models require 1.97in (50mm) minimum.
1. The same space is required horizontally and vertically for both Open Chassis (IP00) and Enclosed Wall-
mounted (IP20, NEMA 1 Type 1) Drives.
2. Always remove the protection covers before installing a 200-240 or 380-480 V Class Drive with an output
of 15 kW or less in a panel.
IMPORTANT
Always provide enough space for suspension eye bolts and the main circuit lines when installing a 200-240
or 380-480 V Class Drive with an output of 18.5 kW or more in a panel.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1.2in
(30.5mm) minimum
Fig 1.8 Drive Installation Orientation and Space

Installation Orientation and Space

4.72in (120mm) minimum
4.75in (120mm) minimum
Vertical Clearance