Parameter
Number
E1-13
* 2. The factory setting will change when the control method is changed. (Open-loop vector 1 factory settings are given.)
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. E1-13 is set to the same value as E1-05 by Autotuning.
* 5. Setting range changes to 0 thru 66.0 when operating in Vector 2 wo/PG . The upper limit for the setting range also depends on the upper limit in E1-04.
Motor Setup: E2
Parameter
Number
E2-01
E2-02
E2-03
E2-04
E2-05
E2-06
E2-07
E2-08
-36
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Description
Display
Base
Set only when the V/F pattern is
Voltage
finely adjusted in the constant
power (HP) area above base speed.
Adjustment is not normally
Base
required.If E1-13 = 0.0, then value
Voltage
in E1-05 is used for E1-13.
Auto-Tuning sets this value.
Name
Description
Display
Motor Rated
Sets the motor nameplate full
current
load current in amperes (A).
This value is automatically
Motor Rated
set during Auto-Tuning.
FLA
Motor Rated
Sets the motor rated slip in
Slip
hertz (Hz). This value is
automatically set during
Motor Rated
rotational Auto-Tuning.
Slip
Motor No-
Sets the magnetizing current
load Current
of the motor as a percentage
of full load amps (E2-01).
This value is automatically
No-Load
set during rotational Auto-
Current
Tuning.
Number of
Sets the number of motor
Motor Poles
poles.
This value is automatically
Number of
set during Auto-Tuning.
Poles
Motor
Sets the phase-to-phase motor
Line-to-line
resistance in ohms.
Resistance
This value is automatically
Term
set by Auto-Tuning.
Resistance
Motor Leak
Sets the voltage drop due to
Inductance
motor leakage inductance as a
percentage of the motor rated
voltage.
Leak
This parameter is automatically
Inductance
set during Auto-Tuning.
Motor
Sets the motor iron saturation
Iron-core
coefficient at 50% of
Saturation
magnetic flux.
Coefficient 1
This value is automatically
set during rotational
Saturation
Auto-Tuning.
Comp1
Motor
Sets the motor iron saturation
Iron-core
coefficient at 75% of
Saturation
magnetic flux.
Coefficient 2
This value is automatically
set during rotational
Saturation
Auto-Tuning.
Comp2
Change
Setting
Factory
during
Range
Setting
V/f
Operation
0.0
to
255.0
0.0
(240V)
No
A
Vac
0.0
*4
to
510.0
(480V)
Control Methods
Change
Setting
Factory
V/f
during
Range
Setting
V/f
with
Operation
PG
0.32
to
1.90 A
No
Q
6.40
*1
*2
0.00
2.90Hz
to
No
A
*1
20.00
0.00
to
1.20 A
No
A
1.89
*1
*3
2 to 48
4 poles
No
No
0.000
9.842 Ω
to
No
A
*1
65.000
0.0
18.2%
to
No
No
No
*1
40.0
0.00
to
0.50
No
No
No
0.50
0.5
to
0.75
No
No
No
0.75
Control Methods
Open
Open
MODBUS
V/f
Loop
Flux
Loop
Register
with
Vector
Vector
Vector
PG
1
2
A
Q
Q
Q
30CH
Open
Open
MODBUS
Loop
Flux
Loop
Register
Vector
Vector
Vector
1
2
Q
Q
Q
Q
30EH
A
A
A
A
30FH
A
A
A
A
310H
Q
No
Q
Q
311H
A
A
A
A
312H
A
A
A
313H
A
A
A
314H
A
A
A
315H