Parameter
Number
b1-03
C6-02
C6-11
d1-01 to
d1-04 and
d1-17
H4-02
and H4-
05
L3-04
-6
4
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 4.2 Parameters that Are Set as Required
Name
Select stopping method when stop command is
sent.
Stopping method
0: Deceleration to stop
selection
1: Coast to stop
2: DC braking stop
3: Coast to stop with timer
Carrier fre-
quency selection
The carrier frequency is set low if the motor cable
is 50 m or longer or to reduce radio noise or leak-
age current.
Carrier fre-
quency selection
for open-loop
vector control 2
Frequency refer-
ences 1 to 4 and
Set the required speed references for multi-step
jog frequency ref-
speed operation or jogging.
erence
FM and AM ter-
Adjust when an instrument is connected to the FM
minal output gain
or AM terminal.
If using the dynamic brake option (braking resis-
Stall prevention
tor, Braking Resistor Units, and Braking Units), be
selection during
sure to set parameter L3-04 to 0 (disabled) or 3
deceleration
(enabled with braking resistor).
Description
Setting
Factory
Range
Setting
0 to 3
0
Depends
on capac-
ity, volt-
1 to F
age, and
control
mode.
Depends
1 to 4
on kVA
setting.
d1-01 to
d1-04:
0.00 to
0.00Hz
400.00 Hz
d1-17:
6.00Hz
H4-02:
100%
0.0 to 1000.0
H4-05:
50%
0 to 3
1