YASKAWA G7 Series Technical Manual page 363

Table of Contents

Advertisement

Error displays and their meanings are shown below. (Refer to Chapter 7 Errors when Using the Digital Oper-
ator Copy Function.)
Error Display
PRE
READ IMPOSSIBLE
IFE
READ DATA ERROR
RDE
DATA ERROR
Select READ Permitted
Prevent overwriting the data stored in EEPROM in the Digital Operator by mistake. With o3-02 set to 0, if you
set o3-01 to 1, and perform the write operation, PrE will be displayed on the Digital Operator, and the write
operation will be stopped.
Writing Parameter Set Values Stored in the Digital Operator to the Drive (COPY)
To write parameter set values stored in the Digital Operator to the Drive, make the settings using the following
method.
Step
Digital Operator Display
No.
-ADV-
** Main Menu **
1
Programming
-ADV-
Initialization
2
A1
- 00=1
Select Language
-ADV-
COPY Function
3
o3
- 01=0
Copy Funtion Sel
-ADV-
Copy Funtion Sel
4
o3-01=
0
*0*
COPY SELECT
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
You are attempting to set o3-01 to 1 while o3-02 is set to 0.
Read data length mismatch or read data error.
Tried to write parameters to EEPROM on the Digital Operator, but unable to perform
write operation.
Table 6.2 COPY Function Procedure
Press the MENU Key, and select advanced programming mode.
Press the DATA/ENTER Key, and select the parameter monitor display.
Display o3-01 (Copy Function Selection) using the Increment Key and Decrement
Key.
Press the DATA/ENTER Key, and select the parameter setting display.
Digital Operator Functions
Meaning
Explanation
145
6-