Hunting-prevention Function

The hunting-prevention function suppresses hunting when the motor is operating with a light load. This func-
tion can be used in V/f without PG and V/f with PG.
Related Parameters
Name
Parameter
Number
Display
Hunting
If the motor vibrates while lightly
Prevention
loaded, hunting
Selection
prevention may reduce the
n1-01
vibration.
Hunt Prev
0: Disabled
Select
1: Enabled
Hunting
Sets the gain for the Hunting
Prevention
Prevention Function.
Gain Setting
If the motor vibrates while lightly
loaded and n1-01=1, increase the
n1-02
gain by 0.1 until vibration ceases.
If the motor stalls while n1-01=1,
Hunt Prev Gain
decrease the gain by 0.1 until the
stalling ceases.