The motor torque limit function is enabled only with open-loop torque control.
In the open-loop vector control method, the user-set value is applied to the torque limit by calculating inter-
nally the torque output by the motor. Enable this function if you do not want a torque above a specified
amount to be applied to the load, or if you do not want a regeneration value above a specified amount to occur.
Related Parameters
Parame-
ter
Number
Forward
Torque
Limit
L7-01
Torq Limit
Fwd
Reverse
Torque
Limit
L7-02
Torq Limit
Rev
Forward
Regenera-
tive Torque
L7-03
Limit
Torq Lmt
Fwd Rgn
Reverse
Regenera-
tive Torque
L7-04
Limit
Torq Lmt
Rev Rgn
Multi-function Analog Input (H3-05, H3-09)
Setting
Value
10
Positive torque limit
11
Negative torque limit
12
Regenerative torque limit
15
Positive/negative torque limit
Note The forward torque limit is the limit value when the analog input signal generates forward torque. This torque limit setting is enabled even when the
analog input signal generates forward torque while the motor is operating (regeneration).