YASKAWA G7 Series Technical Manual page 120

Table of Contents

Advertisement

Parameter
Number
Display
Terminal
FM Gain
Setting
H4-02
Terminal
FM Gain
Terminal
AM Gain
Setting
H4-05
Terminal
AM Gain
Motor
Overload
Protection
L1-01
Selection
MOL Fault
Select
-8
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Description
Sets terminal FM output level when
selected monitor is at 100%.In order to
adjust the meter, 100% of the
appropriate output is multiplied for the
gain setting, the bias amount is added
and then output.
See H4-02 when stopped in Quick,
Advanced, or Verify mode. If 03
appears on the setting screen, then
terminal FM is used.
See H4-04 when stopped in Quick,
Advanced, or Verify mode. If 06
appears on the setting screen, then
terminal AM is used.
Sets terminal AM output voltage (in
percent of 10Vdc) when selected
monitor is at 100% output. In order to
adjust the meter, 100% of the
appropriate output is multiplied for the
gain setting, the bias amount is added
and then output.
See H4-02 when stopped in Quick,
Advanced, or Verify mode. If 03
appears on the setting screen, then
terminal FM is used.
See H4-04 when stopped in Quick,
Advanced, or Verify mode. If 06
appears on the setting screen, then
terminal AM is used.
Sets the motor thermal overload
protection (OL1) based on the cooling
capacity of the motor.
0: Disabled
1: Standard Fan Cooled (< 10:1 motor)
2: Standard Blower Cooled (
3: Vector Motor (
1000:1 motor)
Change
Setting
Factory
during
Range
Setting
Operation
0.00
to
100%
1000.0
0.00
to
50%
1000.0
0 to 3
1
10:1 motor)
Control Methods
Open
Open
V/f
-loop
Flux
Loop
V/f
with
Vector
Vector
Vector
PG
1
Yes
Q
Q
Q
Q
Yes
Q
Q
Q
Q
No
Q
Q
Q
Q
MODBUS
Register
2
Q
41EH
Q
421H
Q
480H