YASKAWA G7 Series Technical Manual page 157

Table of Contents

Advertisement

Digital Reference Card: F3
User parameters for the Digital Reference Card are shown in the following table.
Name
Parameter
Number
Display
DI-08 /
Sets the function of the DI-08
DI-16H2
or the DI-16H2 digital input
Input
option board.
Selection
0: BCD 1% unit
1: BCD 0.1% unit
2: BCD 0.01% unit
3: BCD 1Hz unit
4: BCD 0.1Hz unit
F3-01
5: BCD 0.01Hz unit
6: BCD (5-digit) 0.01Hz unit
(only effective when
DI Input
DI-16H2 is used.)
7: Binary input
When o1-03 is set to 2 or
higher, the input will be BCD,
and the units will change to
the o1-03 setting.
Analog Monitor Cards: F4
User parameters for the Analog Monitor Card are shown in the following table.
Name
Parameter
Number
Display
AO-08/
Sets the number of the
AO-12
monitor item to be output.
Channel 1
(U1-oo). The following
F4-01
Monitor
settings cannot be used:
Selection
4, 10 to 14, 25, 28, 29, 30, 34,
35, 39, 40, 41.
AO Ch1 Sel
AO-08/
Sets the channel 1 gain.
AO-12
Ex: Set F4-02 = 50% to
Channel 1
F4-02
output 100% at 5.0V
Gain
output.
AO Ch1 Gain
AO-08/
Sets the number of the
AO-12
monitor item to be output.
Channel 2
(U1-xx). The following
Monitor
F4-03
settings cannot be set:
Selection
4, 10 to 14, 25, 28, 29, 30,
AO Ch2
34, 39, 40, 41.
Select
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting
Factory
Description
Range
Setting
0 to 7
Setting
Factory
Description
Range
Setting
1 to 45
0.0
to
100%
1000.0
1 to 45
User Parameter Tables
Control Methods
Change
Open
V/f
during
Loop
V/f
with
Operation
Vector
PG
1
0
No
A
A
A
Control Methods
Change
Open
V/f
during
Loop
V/f
with
Operation
Vector
PG
1
2
No
A
A
A
Yes
A
A
A
3
No
A
A
A
Open
MODBUS
Flux
Loop
Register
Vector
Vector
2
A
A
390H
Open
MODBUS
Flux
Loop
Register
Vector
Vector
2
A
A
391H
A
A
392H
A
A
393H
45
5-