Operation Errors - YASKAWA G7 Series Technical Manual

Table of Contents

Advertisement

Operation Errors

An operation error will occur if there is an invalid setting or a contradiction between two parameter settings. It
won't be possible to start the Drive until the parameters have been set correctly. (The alarm output and fault
contact outputs will not operate either.)
When an operation error has occurred, refer to the following table to identify and correct the cause of the
errors.
Table 7.3 Operation Error Displays and Incorrect Settings
Display
Meaning
OPE01
Incorrect Drive capacity
kVA Selec-
setting
tion
OPE02
Parameter setting range
Limit
error
Multi-function input
OPE03
selection error
Terminal
OPE05
Option Card selection
Sequence
error
Select
OPE06
Control method selec-
PG Opt Miss-
tion error
ing
OPE07
Multi-function analog
Analog
input selection error
Selection
Parameter selection
OPE08
error
PID control selection
OPE09
error
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
The Drive capacity setting doesn't match the Unit. (Contact your Yaskawa represen-
tative.)
The parameter setting is outside of the valid setting range. When this error is dis-
played, press the ENTER Key to display U1-34 (
One of the following errors has been made in the multi-function input (H1-01 to H1-
10) settings:
• The same setting has been selected for two or more multi-function inputs.
• An up or down command was selected independently. (They must be used
together.)
• The up/down commands (10 and 11) and Accel/Decel Ramp Hold (A) were
selected at the same time.
• Speed Search 1 (61, maximum output frequency) and Speed Search 2 (62. set fre-
quency) were selected at the same time.
• The up/down commands (10 and 11) were selected while PID Control Mode
Selection (b5-01) was enabled.
• Positive and negative speed commands have not been set at the same time.
• The emergency stop command NO and NC have been set at the same time.
The Option Card was selected as the frequency reference source by setting b1-01 to
3, but an Option Card isn't connected (C option).
V/f control with PG feedback was selected by setting A1-02 to 1, but a PG Speed
Control Card isn't connected.
The same setting has been selected for the analog input selection and the PID func-
tion selection.
• H3-09 = B and H6-01 = 1
• H3-09 = C and H6-01 = 2
b1-01 (Reference Selection) is set to 4 (pulse input) and H6-01 (Pulse Train Input
Function Selection) is set to a value other than 0 (frequency reference).
A setting has been made that is not required in the current control method. Ex.: A
function used only with open-loop vector control was selected for V/f control. When
this error is displayed, press the ENTER Key to display U1-34 (
The following settings have been made at the same time.
• b5-01 (PID Control Mode Selection) has been set to a value other than 0.
• b5-15 (PID Sleep Function Operation Level) has been set to a value other than 0.
• b1-03 (Stopping Method Selection) has been set to 2 or 3.
Protective and Diagnostic Functions
Incorrect settings
OPE fault parameter)
OPE fault parameter)
.
.
13
7-