No.
Type
+V
-V
A1
A2
Analog
input
signals
A3
AC
E(G)
P3
Photo-
C3
coupler
outputs
P4
C4
-24
2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 2.10 Control Circuit Terminals (Continued)
Signal Name
+15 V power output
-15 V power output
Master speed frequency
reference
Multi-function analog input
Multi-function analog input
Analog reference common
Shield wire, optional ground
line connection point
Multi-function PHC
output 3
Multi-function PHC
output 4
Function
+15 V power supply for analog input
or transmitters
-15 V power supply for analog input
or transmitters
-10 to +10 V/-100 to 100%
0 to +10 V/100%
4 to 20 mA/100%, -10 to +10 V/-100 to
+100%, 0 to +10 V/100%
4 to 20 mA/100%, -10 to +10 V/-100 to
+100%, 0 to +10 V/100%
0 V
-
Factory setting: Ready for operation when CLOSED.
Factory setting: FOUT frequency detected when
CLOSED.
Signal Level
+15 V
(Max. current: 20
mA)
-15 V
(Max. current: 20
mA)
-10 to +10 V, 0 to
+10 V (Input imped-
ance: 20 kΩ)
Multi-
function
analog
4 to 20 mA (Input
impedance: 250 Ω)
input 2.
Function
set by
H3-09
Multi-
function
analog
4 to 20 mA (Input
input 3.
impedance: 250 Ω)
Function
set by
H3-05
-
-
50 mA max. at 48
*2
Vdc