Parameter
Number
AO-08/AO-
12 Channel 1
Monitor
F4-01
Selection
AO Ch1
Select
AO-08/AO-
12 Channel 1
F4-02
Gain
AO Ch1 Gain
AO-08/AO-
12 Channel 2
Monitor
F4-03
Selection
AO Ch2
Select
AO-08/AO-
12 Channel 2
F4-04
Gain
AO Ch2 Gain
AO Ch1 Bias Sets the channel 1 bias (100%/10V).
F4-05
AO Ch1 Bias
AO Ch2 Bias Sets the channel 2 bias (100%/10V).
F4-06
AO Ch2 Bias
AO-12
Channel 1
Signal Level
F4-07
AO Opt
Level Sel
AO-12
Channel 2
Signal Level
F4-08
AO Opt
Level Sel
1
*
In order to adjust the meter, 100% of the appropriate output is multiplied for the gain setting, the bias amount is added and then output.
See H4-02 when stopped in Quick, Advanced, or Verify mode. If 03 appears on the setting screen, then terminal FM is used.
See H4-04 when stopped in Quick, Advanced, or Verify mode. If 06 appears on the setting screen, then terminal AM is used.
2
*
Setting "2: 4 to 20mA" is not available in F7A
3
*
In order to adjust the meter, 100% of the appropriate output is multiplied for the gain setting, and the bias amount is added and then output.
See F4-02 when stopped in Quick, Advanced, or Verify mode. If 05 appears on the setting screen, then CH1 is used.
See F4-04 when stopped in Quick, Advanced, or Verify mode. If 06 appears on the setting screen, then CH2 is used.
-80
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Description
Display
Sets the number of the monitor item
to be output. (U1-oo)
The following settings cannot be
used:
4, 10 to 14, 25, 28, 29, 30, 34, 35,
39, 40, 41.
Sets the channel 1 gain.
Ex: Set F4-02 = 50% to output
100% at 5.0V output.
Sets the number of the monitor item
to be output. (U1-xx)
The following settings cannot be
set:
4, 10 to 14, 25, 28, 29, 30, 34, 39,
40, 41.
Sets the channel 2 gain. *
Ex: Set F4-04 = 50% to output
100% at 5.0V output.
Ex: Set F4-05 = 50% to output 0%
at 5.0V output.
Ex: Set F4-06 = 50% to output 0%
at 5.0V output.
Sets the range of the voltage
output.
0: 0 to 10Vdc
1: -10 to +10Vdc
Sets the range of the voltage
output.
0: 0 to 10Vdc
1: -10 to +10Vdc
Change
Setting
Factory
Range
Setting
Operation
1 to 45
2
0.00
to
100.0%
1000.0
1 to 45
3
3
0.00
to
50.0%
1000.0
-110.0
to
0.0%
110.0
-110.0
to
0.0%
110.0
0 to 1
0
0 to 1
0
Control Methods
Open
V/f
during
Loop
Flux
V/f
with
Vector
Vector
PG
1
No
A
A
A
A
Yes
A
A
A
A
No
A
A
A
A
Yes
A
A
A
A
Yes
A
A
A
A
Yes
A
A
A
A
No
A
A
A
A
No
A
A
A
A
Open
Loop
Vector
2
A
A
A
A
A
A
A
A