No.
Signal Name
Type
Fault output signal
MA
(NO contact)
Fault output signal
MB
(NC contact)
Relay contact output
MC
common
M1
Multi-function contact
output
M2
(NO contact)
Relay
outputs
M3
Multi-function contact
output 2
M4
M5
Multi-function contact
output 3
M6
Multi-function analog
FM
monitor 1
Analog
monitor
outputs
Multi-function analog
AM
monitor 2
AC
Analog common
RP
Multi-function pulse input
Pulse
I/O
Multi-function pulse
MP
monitor
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 2.10 Control Circuit Terminals (Continued)
MA / MC: Closed during fault condition
MB / MC: Open during fault condition
Factory setting: Operating
Operating when CLOSED across M1 and
M2.
Factory setting: Zero speed
Zero speed level (b2-01) or below when
CLOSED.
Factory setting: Frequency
agreement detection
Frequency within 2 Hz of set
frequency when CLOSED.
0 to +10Vdc / 100% frequency
-10 to +10Vdc / 100% frequency
4 to 20mA / 100% frequency
0 to +10Vdc / 100% Drive's rated
output current
-10 to +10Vdc / 100% Drive's rated output
current
4 to 20mA / 100% Drive's rated output cur-
rent
*3
Factory setting: Frequency reference
Factory setting: Output frequency
Wiring Control Circuit Terminals
Function
-
Multi-
function
digital
output.
Function
set by
H2-01
Multi-
function
digital
output.
Function
set by
H2-02
Multi-
function
digital
output.
Function
set by
H2-03
Multi-
function
analog
output 1.
Function
set by
H4-01
Multi-
function
analog
output 2.
Function
set by
H4-04
-
Function
set by
H6-01
Function
set by
H6-06
Signal Level
Form C
Dry contacts
capacity:
1 A max. at 250 Vac
1 A max. at 30 Vdc
Form A
Dry contacts
capacity:
1 A max. at 250 Vac
1 A max. at 30 Vdc
0 to +10 Vdc ±5%
2 mA max.
0 to 32 kHz (3 kΩ)
0 to 32 kHz (2.2 kΩ)
25
2-