YASKAWA G7 Series Technical Manual page 239

Table of Contents

Advertisement

Time Chart
The following figure shows the frequency characteristics when L3-01 is set to 1.
Output current
Stall level during
acceleration
Output frequency
Fig 6.21 Time Chart for Stall Prevention During Acceleration
Setting Precautions
If the motor capacity is small compared to the Drive capacity, or if the motor is operated using the factory
settings, resulting in the motor stalling, lower the set value of L3-02.
If using the motor in the constant output range, L3-02 will be automatically lowered to prevent stalling.
L3-03 is the limit value to prevent the stall prevention level in the constant output range from being
reduced more than necessary.
Set the parameters as a percent taking the drive rated voltage to be 100%.
Stall prevention level during
acceleration
Fig 6.22 Stall Prevention Level and Limit During Acceleration
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Output frequency is controlled
to prevent the motor stalling.
E1-06
Base Frequency (FA)
Acceleration and Deceleration Characteristics
Time
Time
L3-02 (Stall Prevention Level during Accelera-
tion)
L3-02 x L3-03 (Stall Prevention Limit during Ac-
celeration)
Output frequency
21
6-

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents