An error may occur during the comparison. If an error is displayed, press any key to cancel the error display
and return to the o3-01 display. Error displays and their meanings are shown below. (Refer to Chapter 7
Errors when Using Digital Operator Copy Function.)
Error Display
VERIFY ERROR
Application Precautions
When using the copy function, check that the following settings are the same between the Drive and the Digi-
tal Operator.
Drive product and type
Software number

Prohibiting Writing Parameters from the Digital Operator

If you set A1-01 to 0, you can refer to and set the A1 and A2 parameter groups, and refer to drive mode, using
the Digital Operator.
If you set one of the parameters H1-01 to H1-05 (multi-function contact input terminal S3 to S7 function
selection) to 1B (write parameters permitted), you can write parameters from the digital operator when the ter-
minal that has been set is ON. When the set terminal is OFF, writing parameters other than the frequency ref-
erence is prohibited. You can, however, reference parameters.
Parameter
Number
Access Level
Selection
A1-01
Access Level
-148
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
VYE
Verify error (Settings in the Digital Operator and the Drive do not match).
Name
Description
Display
Selects which parameters are
accessible via the Digital
Operator.
0: Operation Only
1: User Level (only available if
A2 parameters have been set)
2: Advanced Level
Meaning
Drive capacity and voltage
Control method
Change
Setting
Factory
during
Range
Setting
Operation
0 to 2
2
Yes
Control Methods
Open
Open
V/f
Loop
Flux
Loop
V/f
with
Vector
Vector
Vector
PG
1
2
A
A
A
A
A