PG-B2
The terminal specifications for the PG-B2 are given in the following table.
Terminal
TA1
TA2
TA3
PG-D2
The terminal specifications for the PG-D2 are given in the following table.
Terminal
TA1
TA2
* 5 Vdc and 12 Vdc cannot be used at the same time.
-34
2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 2.16 PG-B2 Terminal Specifications
No.
Contents
1
Power supply for pulse generator
2
3
A-phase pulse input terminal
4
5
B-phase pulse input terminal
6
1
A-phase monitor output terminal
2
3
B-phase monitor output terminal
4
(E)
Shield connection terminal
Table 2.17 PG-D2 Terminal Specifications
No.
Contents
1
2
Power supply for pulse generator
3
4
Pulse input + terminal
5
Pulse input - terminal
6
Common terminal
7
Pulse monitor output + terminal
8
Pulse monitor output - terminal
(E)
Shield connection terminal
Specifications
12 Vdc (±5%), 200 mA max.
0 Vdc (GND for power supply)
H: +8 to 12 Vdc
L: +1 Vdc max.
(Maximum response frequency: 30 kHz)
Pulse input common
H: +8 to 12 Vdc
L: +1 Vdc max.
(Maximum response frequency: 30 kHz)
Pulse input common
Open collector output, 24 Vdc, 30 mA max.
A-phase monitor output common
Open collector output, 24 Vdc, 30 mA max.
B-phase monitor output common
-
Specifications
12 Vdc (±5%), 200 mA max.*
0 Vdc (GND for power supply)
5 Vdc (±5%), 200 mA max.*
Line driver input (RS-422 level input)
Maximum response frequency: 300 kHz
-
Line driver output (RS-422 level output)
-