4/0
250 / 300MCM
400MCM
650MCM
*
Wire sizes are based on 75 degrees Celsius copper wire.
** Equivalent connector can be used.
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:
Line voltage drop (V) =
IMPORTANT
-12
2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Wire Size *
100
125 / 150
200
325
3
x wire resistance (W/km) x wire length (m) x current (A) x 10
Ring Tongue (R-Type) Closed-Loop Connectors (Lugs)
Terminal Screw
M10
M12
M16
M10
M12
M16
M12
M12 x 2
M16
JST Corporation Part Numbers **
100 - 10
100 - 12
100 - 16
150 - 10
150 - 12
150 - 16
200 - 12
325 - 12
325 - 16
-3