H3-05,H3-09 Settings
Setting
Function
Value
0
Frequency Bias
Frequency Reference Gain
1
(FGAIN)
2
Aux Frequency Reference 1
3
Aux Frequency Reference 2
4
Output Voltage Bias
5
Accel / Decel Time Coefficient
6
DC Injection Braking Current
Overtorque / Undertorque
7
Detection Level
8
Stall Prevention Level During Run 100% = L3-06.
9
Frequency Reference Lower Limit
A
Jump Frequency
B
PID Feedback
C
PID Set Point
D
Frequency Reference Bias 2
E
Motor Temperature Input
10
FWD Torque Limit (Quadrant 1)
11
REV Torque Limit (Quadrant 3)
Regenerative Torque Limit (Quad-
12
rants 2 and 4)
Torque Reference (in Torque Con-
13
trol); Torque Limit (in Speed Con-
trol)
14
Torque Compensation
15
FWD / REV Torque Limit
1F
Analog input not used.
16 to 1E
Not used
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Contents (100%)
100% = Maximum output frequency (E1-04)
100% = Frequency reference command value A1
Total gain = Internal gain (H3-02) x FGAIN
Used in conjunction with multi-function inputs
"multi-step frequency reference 1-4" (d1-16).
100% = Maximum output frequency (E1-04)
Used in conjunction with multi-function inputs
"multi-step frequency reference 1-4" (d1-16).
100% = Maximum output frequency (E1-04)
100% = Motor rated voltage (E1-05).
Voltage boost after V/F pattern
100% = Active accel / decel time (C1-01 thru C1-08)
100% = Drive rated current.
Parameter b2-02 is disabled.
Used for multi-function digital output for
"overtorque/undertorque".
100% = motor rated torque (OLV, FV) or Drive rated
current (V/F, V/F w/PG).
Internal overtorque detection level (C6-02) disabled.
100% = Maximum output frequency (E1-04).
Either the setting in d2-02 or the A3 input level is
enabled, whichever is larger.
100% = Maximum output frequency (E1-04).
100% = Maximum output frequency (E1-04).
100% = Maximum output frequency (E1-04).
Frequency reference no longer acts as a PID setpoint.
100% = Maximum output frequency
(E1-04).
Total bias = Internal bias (H3-03) + FBIAS (H3-07) +
A3 input level
10V = 100%
See parameters L1-03 and L1-04
100% = Motor rated torque.
100% = Motor rated torque.
100% = Motor rated torque.
100% = Motor rated torque.
100% = Motor rated torque.
100% = Motor rated torque.
-
-
User Parameter Tables
Control Methods
Open
Open
V/f
Loop
Flux
Loop
V/f
with
Vector
Vector
Vector
PG
1
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
-
-
-