Name
Parameter
Number
Display
KEB
Sets the time required to
Deceleration
decelerate to zero speed when a
Rate
L2-06
KEB command is input from a
KEB Decel
multi-function input.
Time
Momentary
Set the time (in seconds) to
Recovery
accelerate to the set speed after
Time
recovery from a momentary
L2-07
power loss. If setting = 0.0,
UV Return
then active acceleration time is
Time
used instead.
Frequency
Sets the percentage of output
Reduction
frequency reduction at the
Gain at
beginning of deceleration when
KEB Start
a KEB command is input from
L2-08
multi-function input.
Reduction =
KEB
(SlipFreqBeforeKEB) x L2-08
Frequency
x 2
* 1. Factory settings will vary based on drive capacity (values given here are for 208-240Vac, 0.4kW).
* 2. Setting value for 208-240Vac. Double the value when working with 380-480Vac drives.
* 3. When set to zero, the motor will accelerate to the speed set acceleration time (C1-01 thru C1-08).
Stall Prevention: L3
User parameters for the stall prevention function are shown in the following table.
Name
Parameter
Number
Display
Stall
Selects the stall prevention
Prevention
method used to prevent
Selection
excessive current during
During
acceleration.
Accel
0: Disabled - Motor
accelerates at active
acceleration rate. The motor
may stall if load is too
heavy or accel time is too
short.
1: General Purpose - When
L3-01
output current exceeds
L3-02 level, acceleration
stops. Acceleration will
StallP
continue when the output
Accel Sel
current level falls below the
L3-02 level.
2: Intelligent - The active
acceleration rate is ignored.
Acceleration is completed
in the shortest amount of
time without exceeding the
current value set in L3-02.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting
Factory
Description
Range
Setting
0.0
to
0.0sec
200.0
0.0
0.0sec
to
25.5
0
to
100%
300
Setting
Factory
Description
Range
Setting
0 to 2
User Parameter Tables
Control Methods
Change
Open
V/f
during
Loop
V/f
with
Operation
Vector
PG
1
No
A
A
A
No
A
A
A
*3
No
A
A
A
Control Methods
Change
Open
V/f
during
Loop
V/f
with
Operation
Vector
PG
1
1
No
A
A
A
Open
MODBUS
Flux
Loop
Register
Vector
Vector
2
A
A
48AH
A
A
48BH
A
A
48CH
Open
MODBUS
Flux
Loop
Register
Vector
Vector
2
No
No
48FH
63
5-