Input Terminal Functions

This section explains input terminal functions, which set operating methods by switching functions for the
multi-function contact input terminals (S3 to S12).
Temporarily Switching Operation between Digital Operator and Control
Circuit Terminals
You can switch the Drive run command inputs and frequency reference inputs between local (i.e., Digital
Operator) and remote (input method using b1-01 and b1-02).
You can switch between local and remote by turning ON and OFF the terminals if an output from H1-01 to
H1-10 (multi-function contact input terminal S3 to S12 function selection) has been set to 1 (local/remote
selection).
To set the control circuit terminals to remote, set b1-01 and b1-02 to 1 (Control circuit terminals).
Related Parameters
Name
Parameter
Number
Display
Frequency
Reference
Selection
b1-01
Reference
Source
Run
Command
Selection
b1-02
Run Source
You can also perform local/remote switching using the LOCAL/REMOTE Key on the Digital Operator. When
the local/remote function has been set in the external terminals, the LOCAL/REMOTE Key function on the
Digital Operator will be disabled.
INFO
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Selects the frequency reference
input source.
0: Operator - Digital preset speed
U1-01 or d1-01 to d1-17.
1: Terminals - Analog input
terminal A1 (or terminal A2
based on parameter H3-09).
2: Serial Com - Modbus RS-422/
485 terminals R+, R-,
S+, and S-.
3: Option PCB - Option board
connected on 2CN.
4: Pulse Input (Terminal RP)
Selects the run command input
source.
0: Operator - RUN and STOP
keys on Digital Operator.
1: Terminals - Contact closure on
terminals S1 or S2.
2: Serial Com - Modbus RS-422/
485 terminals R+, R-,
S+, and S-.
3: Option PCB - Option board
connected on 2CN.
Change
Setting
Factory
during
Range
Setting
V/f
Operation
0 to 4
1
No
Q
0 to 3
1
No
Q
Input Terminal Functions
Control Methods
Open
Open
V/f
Loop
Flux
Loop
with
Vector
Vector
Vector
PG
1
2
Q
Q
Q
Q
Q
Q
Q
Q
69
6-