YASKAWA G7 Series Technical Manual page 85

Table of Contents

Advertisement

Setting User Parameters
Here, the procedure is shown to change C1-01 (Acceleration Time 1) from 10 s to 20 s.
Table 3.8 Setting User Parameters in Advanced Programming Mode
Step
Digital Operator Display
No.
Rdy
-DRIVE-
Frequency Ref
U1- 01=60.00Hz
1
U1-02=60.00Hz
U1-03=10.05A
-DRIVE-
** Main Menu **
2
Operation
-QUICK-
** Main Menu **
3
Quick Setting
-ADV-
** Main Menu **
4
Programming
-ADV-
Initialization
5
A1-00=1
Select Language
-ADV-
Accel Time 1
6
C1-00= 10.0Sec
(0.0
6000.0)
10.0Sec
-ADV-
Accel Time 1
7
C1-01=
0
010.0Sec
-ADV-
Accel Time 1
8
C1-01= 0 010.0Sec
-ADV-
Accel Time 1
9
C1-01= 00 10.0Sec
-ADV-
Accel Time 1
10
C1-01= 00 20.0Sec
-ADV-
Entry Accepted
11
-ADV-
Accel Time 1
12
C1- 01= 20.0Sec
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Power supply turned ON.
MENU Key pressed to enter drive mode.
MENU Key pressed to enter quick programming mode.
MENU Key pressed to enter advanced programming mode.
DATA/ENTER pressed to access monitor display.
Increment or Decrement Key pressed to display C1-01 (Acceleration Time 1).
DATA/ENTER Key pressed to access setting display. The setting of C1-01
(10.00) is displayed.
Shift/RESET Key pressed to move the flashing digit to the right.
Increment Key pressed to change set value to 20.00 s.
DATA/ENTER Key pressed to enter the set data.
"Entry Accepted" is displayed for 1.0 s after the data setting has been con-
firmed with the DATA/ENTER Key.
The monitor display for C1-01 returns.
Drive Mode Indicators
Description
11
3-

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents