UL Markings
The G7 is UL listed to UL Standard 508C, UL FILE No.: E13145.
Conformance to UL Standard
To comply with UL standard, follow the appropriate installation instructions.
Installation Site
Install the Inverter in a pollution degree 2 environment or equivalent.
Specification of Closed-Loop Connector
The closed-loop connectors must be installed on conductors before installing to terminal blocks.
Use UL Listed closed-loop connectors shown in Table 10.5 below.
Inverter
Model CIMR-G7
2015
2018
2022
2030
2037
2045
2055
2075
2090
2110
4018
4022
4030
4037
4045
4055
4075
4090
4110
4132
4160
4185
4220
4300
-18
10
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 10.5 JST Closed-Loop Connector Model
Input
Wire Size
2 AWG
38-8
2 AWG
38-8
1/0 AWG
60-8
3/0 AWG
80-10
4/0 AWG
100-10
1/0 AWG
60-10 (2 per Ph)
3/0 AWG
80-10 (2 per Ph)
250 kcmil
150-12 (2 per Ph)
400 kcmil
200-12 (2 per Ph)
400 kcmil
200-12 (2 per Ph)
6 AWG
14-6
4 AWG
22-6
2 AWG
38-8
2 AWG
38-8
1/0 AWG
60-8
3/0 AWG
80-10
4/0 AWG
100-10
1/0 AWG
60-10 (2 per Ph)
3/0 AWG
80-10 (2 per Ph)
3/0 AWG
80-12 (2 per Ph)
4/0 AWG
100-12 (2 per Ph)
250 kcmil
150-16 (2 per Ph)
400 kcmil
200-16 (2 per Ph)
650 kcmil
325-16 (2 per Ph)
JST Kit P/N
Input
Output
JST Kit P/N
Wire Size
4 AWG
2 AWG
1/0 AWG
3/0 AWG
4/0 AWG
1/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
300 kcmil
6 AWG
4 AWG
4 AWG
2 AWG
1/0 AWG
3/0 AWG
4/0 AWG
1/0 AWG
3/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
300 kcmil
650 kcmil
Output
JST Kit P/N
22-8
38-8
60-8
80-10
100-10
60-10 (2 per Ph)
80-10 (2 per Ph)
100-12 (2 per Ph)
150-12 (2 per Ph)
150-12 (2 per Ph)
14-6
22-6
22-8
38-8
60-8
80-10
100-10
60-10 (2 per Ph)
80-10 (2 per Ph)
80-12 (2 per Ph)
100-12 (2 per Ph)
150-16 (2 per Ph)
150-16 (2 per Ph)
325-16 (2 per Ph)