Electrostatic discharge (ESD) grounding strap
DC power source cables (not provided) with the cable lugs (provided) attached.
The provided cable lugs in an EX8208 switch are sized for 6 AWG (13.3 mm
DC power source cables that you provide must be 6 AWG (13.3 mm
recommend that you install heat-shrink tubing insulation around the power cables and lugs.
The provided cable lugs in an EX8216 switch are sized for 2 AWG (33.6 mm
DC power source cables that you provide must be 2 AWG (33.6 mm
recommend that you install heat-shrink tubing insulation around the power cables and lugs.
3/8 in. (9.5 mm) nut driver or socket wrench
Phillips (+) screwdriver, number 2
Multimeter
To connect DC power to an EX8200 switch:
1. Attach the electrostatic discharge (ESD) grounding strap to your bare wrist, and connect the strap to
the ESD point on the chassis.
2. Flip the Enable switch on the power supply faceplate to the Standby position.
NOTE:
It might be necessary to slide each power supply partially out of the chassis, in order
to easily connect the DC power source cables to the DC power input terminals. See
a DC Power Supply from an EX8200 Switch" on page
3. Remove the plastic cable cover from the DC power input terminals, using the number 2
Phillips (+) screwdriver to loosen the screw (see
2
), minimum 60°C wire. We
2
), minimum 60°C wire. We
243.
Figure 52 on page
177).
2
) power source cables. The
2
) power source cables. The
"Removing